Top of page top Next Previous


Clear Creek Storage Company, LLC   Original Sheet No. 61 : Effective
FERC Gas Tariff
Clear Creek Storage Company, LLC


                 GENERAL TERMS AND CONDITIONS
                           (Continued)
   
              (4) Liquids.  The Gas shall not contain any
     hydrocarbon fractions that might condense to free liquid in
     the line under normal pipeline operating conditions.
   
              (5) Merchantability.  The Gas shall be
     commercially free from dust, gums, gum-forming constituents,
     dirt, impurities or other solid or liquid matter that might
     interfere with its merchantability or cause injury to or
     interference with proper operation of the lines, regulators,
     meters and other equipment of Clear Creek.  The Gas shall
     also be free of all matter that is deemed hazardous or toxic
     and is subject to regulation by the Environmental Protection
     Agency or any state agency having similar jurisdiction or
     authority.
   
             (6) Oxygen.  The Gas shall not have an oxygen
     content in excess of 10 parts per million by volume and the
     parties shall make every reasonable effort to keep the Gas
     free of oxygen.
   
             (7) Temperature.  The Gas shall be delivered at a
     temperature not in excess of 120 degrees Fahrenheit or less
     than 35 degrees Fahrenheit.
   
             (8) Total Sulfur.  The Gas shall not contain more
     than 5 grains of total sulfur per Mcf, of which not more
     than 2 grains shall be mercaptan sulfur.
   
             (9) Water Vapor.  The Gas shall not contain in
     excess of 5 pounds of water per million cubic feet.
   
         12.2 If any Gas tendered for receipt by Clear Creek
     fails at any time to conform to any of these quality
     specifications, Clear Creek may, without liability therefore
     whatsoever, refuse to accept receipt of any Gas until
     Customer demonstrates that the Gas meets the quality
     specifications.  Clear Creeks refusal to accept non-
     specification Gas does not relieve Customer of any of its
     obligations under this tariff.  Clear Creek will notify
     Customer when its Gas does not conform to specification
     stated herein.
   
        12.3 Clear Creek shall not be required to receive Gas
     for Customers account that does not conform to these
     quality specifications.  Customer shall indemnify Clear
     Creek and hold it harmless from all suits, actions,
     regulatory proceedings, damages, costs, losses and expenses







Issued by: M.B. McGinley, Vice President
Issue date: 03/30/00 Effective date: 06/01/00